Aller au contenu principal
Accès ouvert déclaré 2026 article

Numerical Investigation of Cavity-Width Effects on the Thermal Performance of a Mechanically Ventilated Double-Skin Façade

0Citations signalées, ce qui n’est pas une note de qualité
3Institutions déclarées
3Pays d’affiliation déclarés

Rattachement africain : Tunisie, fr, se. Niveau de preuve : code pays fourni par la source.

Le résumé fourni par la source

Double-skin façades (DSFs) offer a promising building-envelope strategy for improving thermal management by promoting heat’s removal from the façade cavity before it is transferred toward the indoor environment. This study numerically investigates the influence of cavity width on the thermo-fluid performance of a mechanically ventilated DSF under summer operating conditions. A two-dimensional computational fluid dynamics (CFD) model was developed using the RNG k-ε turbulence model together with the discrete ordinates radiation model. Mechanical ventilation was imposed through a velocity inlet of 0.765 m s−1, with an inlet air temperature of 17 °C and a solar radiation intensity of 365.4 W·m−2. The numerical model was validated against published experimental temperature measurements, yielding an average absolute relative error of approximately 5.65%. The validated model was subsequently applied to cavity widths ranging from 0.10 to 0.70 m. Increasing the cavity width substantially modified the airflow development and thermal field. The monitored temperature decreased from 31.66 °C at 0.10 m to 17.64 °C at 0.50 m, while further enlargement produced only minor reductions to 17.43 and 17.28 °C at 0.60 and 0.70 m, respectively. The total heat-transfer rate increased from approximately 1000 W at 0.10 m to a maximum of 1388 W at 0.50 m before slightly decreasing to 1379 and 1376 W at 0.60 and 0.70 m, respectively. This temperature reduction enhances heat removal from the façade cavity, helping to limit heat transfer toward the indoor environment and improve indoor thermal comfort under summer conditions. These results demonstrate a non-monotonic relationship between cavity width and heat-removal performance, with 0.50 m providing the highest heat-transfer rate among the investigated configurations. This result is specific to the geometry, boundary conditions, ventilation rate, and operating conditions considered in the present study. It should not be interpreted as a universally optimal cavity width for mechanically ventilated DSFs. The findings highlight the importance of cavity-width selection in the thermal management and design of mechanically ventilated DSFs for energy-efficient building envelopes.

Ce résumé expose les affirmations des auteurs. BNTIC ne l’interprète pas comme une validation indépendante des résultats.

Le contrôle bibliographique ouvert

DOI retrouvé dans Crossref DOI retrouvé ; titre concordant.

Titre Crossref
Numerical Investigation of Cavity-Width Effects on the Thermal Performance of a Mechanically Ventilated Double-Skin Façade
Date Crossref
10/09/2026
Éditeur
MDPI AG
Type
journal-article

Ce recoupement confirme des métadonnées liées au DOI. Il ne confirme ni la méthode ni les conclusions de l’étude, et il ne compte pas comme une seconde source scientifique indépendante.

Les institutions déclarées

Une affiliation ne permet pas de déduire la nationalité d’un auteur.

Les sujets associés

Solar Energy Systems and TechnologiesBuilding Energy and Comfort OptimizationInfection Control and Ventilation

BNTIC News n’est pas le producteur de ces données. Les publications sont interrogées à la demande dans Crossref, OpenAIRE, DOAJ, Europe PMC, HAL, DataCite, AfricArXiv, ROR et la Banque mondiale, sans clé d’accès. OpenAlex reste optionnel. Aucun service payant n’est nécessaire et aucune donnée externe n’est enregistrée en base. Consulter les sources et leurs limites.