Reducing Pipeline AC Interference by Phase Permutation

0Citations signalées — pas une note de qualité
1Institutions déclarées
1Pays d’affiliation déclarés

Résumé fourni par la source

High-voltage power lines can induce alternating current (AC) voltages on nearby gas pipelines, creating safety and corrosion risks. This article presents a French case study involving three gas pipelines exposed to severe interference from a 225 kV dual-circuit line over 17 km (10.6 mi).A Initial simulations predicted voltages approaching 200 V in the steady state; nine earthing systems were installed to reduce them, but these were not sufficient to meet design criteria. A further study examined conductor arrangement and led to phase permutation on the power line. Field measurements confirmed a major mitigation effect, with voltage levels reduced by about a factor of four and AC current densities significantly lowered.

Ce résumé expose les affirmations des auteurs. BNTIC ne l’interprète pas comme une validation indépendante des résultats.

Contrôle bibliographique ouvert

DOI retrouvé dans Crossref DOI retrouvé ; titre concordant.

Titre Crossref
Reducing Pipeline AC Interference by Phase Permutation
Date Crossref
01/09/2026
Éditeur
Association for Materials Protection and Performance (AMPP)
Type
journal-article

Ce recoupement confirme des métadonnées liées au DOI. Il ne confirme ni la méthode ni les conclusions de l’étude et ne compte pas comme une seconde source scientifique indépendante.

Institutions déclarées

Une affiliation ne permet pas de déduire la nationalité d’un auteur.

Sujets associés

Lightning and Electromagnetic PhenomenaThermal Analysis in Power TransmissionElectrical Fault Detection and Protection

BNTIC News n’est pas le producteur de ces données. Recherche à la demande dans Crossref et Europe PMC, sans clé ; OpenAlex reste optionnel. Aucun service payant requis, aucune réponse conservée. Sources et limites.