DETECTION ALGORITHM FOR FAULTY CONTACT JOINTS IN ELECTRICAL NETWORK
Le résumé fourni par la source
The article proposes a thermoelectric method for monitoring the contact resistance of contact joints in power grids. It describes an algorithm to detect faulty contact joints with resistance exceeding the value specified in regulatory standards. The algorithm is considered using the example of a circuit containing five contact joints and three electrical installations. The algorithm is based on calculating contact resistance from the measured values of thermoelectromotive force and flowing current only at the moment the electrical installation is turned on, which makes it possible to calculate the resistance of the contact through which the electrical installation is connected. By the number of electrical installations being turned on or off, the numbers of the contact joints that make up the power supply circuit of this installation are determined.
Ce résumé expose les affirmations des auteurs. BNTIC ne l’interprète pas comme une validation indépendante des résultats.
Le contrôle bibliographique ouvert
DOI retrouvé dans Crossref DOI retrouvé ; titre concordant.
- Titre Crossref
- DETECTION ALGORITHM FOR FAULTY CONTACT JOINTS IN ELECTRICAL NETWORK
- Date Crossref
- 31/03/2025
- Éditeur
- Karagandy University of the name of academician E.A. Buketov
- Type
- journal-article
Ce recoupement confirme des métadonnées liées au DOI. Il ne confirme ni la méthode ni les conclusions de l’étude, et il ne compte pas comme une seconde source scientifique indépendante.