Bone Cement Fumes Generated in Laminar Airflow Versus Conventionally Ventilated Operating Rooms

1Citations signalées, ce qui n’est pas une note de qualité
2Institutions déclarées
1Pays d’affiliation déclarés

Rattachement africain : us. Niveau de preuve : code pays fourni par la source.

Le résumé fourni par la source

BACKGROUND: Bone cement is commonly utilized in a variety of orthopaedic procedures and contains methylmethacrylate (MMA) monomer. MMA is a colorless, clear, flammable liquid of intense odor. Its vapor concentration in the immediate breathing zone can vary considerably in the operative setting and, in higher concentrations, can become an occupational health hazard. Therefore, reducing MMA vapor is desirable. The aim of this study was to compare the MMA vapor levels emitted during mixing among 5 commercially available cement-mixing systems across 2 operative settings: an operating room (OR) with conventional ventilation (CV) and an OR with laminar airflow (LAF). METHODS: A prospective, in vitro study was conducted at a single hospital in an OR with LAF and in an OR with CV. MMA vapor release during the cement preparation of a SAWBONES femoral canal was measured with use of a calibrated MiniRAE 3000. A total of 5 different vacuum cement-mixing systems were utilized to mix the same cement type according to the manufacturer instructions of each system. MMA vapor concentrations were measured during 5 phases of mixing, and each mixing system was randomly utilized 10 times in each OR. RESULTS: When comparing the MMA concentration levels of each system between the 2 settings, emissions remained generally higher in the CV setting for every system and in nearly every phase. Among the 5 systems analyzed, System #5, the only entirely closed system, had the lowest overall emissions for each of the 5 phases in the CV setting. CONCLUSIONS: This study demonstrated that an operative environment with LAF is conducive to clearing the fumes of MMA during mixing as well as limiting the amount of time that residual fumes linger after mixing. Additionally, the entirely closed cement-mixing system was the most effective in minimizing fume levels within the CV setting. Utilizing this closed system, especially in an OR with CV, may reduce exposure to MMA fumes from bone cement, potentially creating a more favorable working environment. CLINICAL RELEVANCE: This study provides evidence that a closed cement-mixing system utilized under vacuum in both an OR with CV and an OR with LAF is effective in keeping MMA fume levels below those considered harmful by the U.S. Occupational Safety and Health Administration.

Ce résumé expose les affirmations des auteurs. BNTIC ne l’interprète pas comme une validation indépendante des résultats.

Le contrôle bibliographique ouvert

DOI retrouvé dans Crossref DOI retrouvé ; titre concordant.

Titre Crossref
Bone Cement Fumes Generated in Laminar Airflow Versus Conventionally Ventilated Operating Rooms
Date Crossref
28/08/2023
Éditeur
Ovid Technologies (Wolters Kluwer Health)
Type
journal-article

Ce recoupement confirme des métadonnées liées au DOI. Il ne confirme ni la méthode ni les conclusions de l’étude, et il ne compte pas comme une seconde source scientifique indépendante.

Les institutions déclarées

Une affiliation ne permet pas de déduire la nationalité d’un auteur.

Les sujets associés

Dental Research and COVID-19Infection Control and VentilationTotal Knee Arthroplasty Outcomes

BNTIC News n’est pas le producteur de ces données. Les publications sont interrogées à la demande dans Crossref, OpenAIRE, DOAJ, Europe PMC, HAL, DataCite, AfricArXiv, ROR et la Banque mondiale, sans clé d’accès. OpenAlex reste optionnel. Aucun service payant n’est nécessaire et aucune donnée externe n’est enregistrée en base. Consulter les sources et leurs limites.