Determination of benzotriazole in industrial cooling water by fluorescence
Résumé fourni par la source
Benzotriazole is widely used in various industries to inhibit corrosion. Sensitive instruments and methods are needed to determine this compound in industrial cooling water. Fluorescence spectroscopy was used to determine benzotriazole in this application. The optimum wavelength was evaluated as well as the influence of pH, temperature, and common ions. Ultraviolet-visible absorption spectroscopy showed that there were two peaks: 259 nm and 278 nm. The latter wavelength was shown to be optimum for the determination of benzotriazole. The fluorescence intensity was linear with concentration from 0.4–4 mg/L. The pH, temperature, and presence of other ions had little effect on the analysis. The detection limit was 0.155 mg/L. In summary, fluorescence spectroscopy was demonstrated to be convenient, sensitive, and economical for the determination of benzotriazole in industrial cooling water.
Ce résumé expose les affirmations des auteurs. BNTIC ne l’interprète pas comme une validation indépendante des résultats.
Contrôle bibliographique ouvert
DOI retrouvé dans Crossref DOI retrouvé ; titre concordant.
- Titre Crossref
- Determination of benzotriazole in industrial cooling water by fluorescence
- Date Crossref
- 15/08/2016
- Éditeur
- Informa UK Limited
- Type
- journal-article
Ce recoupement confirme des métadonnées liées au DOI. Il ne confirme ni la méthode ni les conclusions de l’étude et ne compte pas comme une seconde source scientifique indépendante.
Institutions déclarées
Une affiliation ne permet pas de déduire la nationalité d’un auteur.